2channel HV control cards inventory and reported failures/repairs Written on 15/04/2008 B.Palan ID Status failure Date Location ------------------------------------------------------------------------ M441 repaired ch2 TRACO TMV2415S from PIT Nov 2007 LBA19-20 M361 repaired ch1 TRACO TMV2415S unknown repair date LBA21-22 M394 repaired ch2 TRACO TMV2415S 31.8.2007 LBA25-26 M447 repaired TRACO TMV2415S OK 31.8.2007 LBA31-32 M339 OK ? M340 OK LBA01-02 M341 OK LBC03-04 M342 OK EBA19-20 M343 Ok LBA23-24 M345 OK LBA27-28 M346 OK LBA29-30 M380 OK LBA17-18 M381 OK LBA03-04 M382 Ok LBA05-06 M383 OK LBA07-08 M384 Ok LBA09-10 M385 Ok LBA11-12 M386 Ok LBA13-14 M387 OK LBA15-16 M442 Ok preventive change of TMV2415S 09.04.2008 LBC05-06 M392 error need change HV IRFU420 ch2,no Switch 830/950V still LBC53-54 Problematic DC/DC converters TRACO TMV2415S (series 0028) that are failing In/Out isolation. The TMV2415S dc/dc converter changed already in ~7 HV units. 07-18 April 2008, planned addition of protection fuses on each HV channel.